FOR IMMEDIATE RELEASE
August 4, 1999
Release # 99-152
|
Company Phone Number: (800) 866-7807
CPSC Consumer Hotline: (800) 638-2772
CPSC Media Contact: Ken Giles, (301) 504-7063
|
CPSC, Mealane Corp. Announce Recall of Star Fire Sprinklers
WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety
Commission (CPSC), Mealane Corp. of Philadelphia, Pa., is voluntarily
recalling up to 1 million "Star" brand fire sprinklers manufactured from
1961 through 1976. These sprinklers could fail in a fire, exposing the
public to bodily injury or death. These sprinklers have been installed
nationwide, primarily in nursing homes. They also may be found in
hospitals, schools, resorts, stores, office buildings, warehouses and
supermarkets.
CPSC reports that 67 percent of the sprinklers that were removed
from locations across the country and submitted for testing to
independent testing laboratories, such as by Underwriters Laboratories
and Factory Mutual Research Corp., failed to activate as they should.
CPSC has received one report of a Star sprinkler allegedly not
functioning in a bedroom fire in a nursing home.
The Star sprinklers being recalled are dry-type models D-1, RD-1, RE-1, E-1 and ME-1 made from 1961 through 1976. The name "Star" appears
on the sprinkler, along with the model number and date of manufacture.
With "dry-type" sprinklers, portions of the pipe do not have water in
them until the sprinkler activates. The former Star Sprinkler Co., of
Philadelphia, Pa., sold its assets and changed its name in June 1976 and
became known as Mealane Corp.
The Joint Commission on Accreditation of Healthcare Organizations,
an independent, not-for-profit organization that evaluates and accredits
hospitals and other long-term-care facilities, is supporting the recall
with CPSC.
Consumers and property owners should determine whether their
facilities contain these recalled sprinklers and if so, call the Star
Sprinkler Recall Hotline at (800) 866-7807 or access the website at
www.star-recall.com to participate in the recall. Mealane will provide
free replacement sprinkler heads and reimbursement for the labor costs
of removing and replacing the old units.
CPSC is continuing its ongoing investigation of fire sprinklers.

|