FOR IMMEDIATE RELEASE
October 2, 2002
Invensys' Recall Hotline: (877) 481-2372
CPSC Consumer Hotline: (800) 638-2772
CPSC Media Contact: Ken Giles, (301) 504-7052

CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Invensys Building Systems, of Love Park, Ill., is recalling up to 560,000 Siebe actuators for testing and replacement, if necessary, which could be found in fire and smoke dampers. Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism, integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam, and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing. The actuators have been identified as IBS or Siebe MA 200 and MA-200-1series with one of the following model numbers: models MA-220, MA-220-0-1, MA-220-0-2, MA-221, MA-221-0-1, MA-221-0-2, MA-223, MA-223-0-1, MA-223-0-2, MA-230, MA 230-0-1, MA-233, MA-233-0-1, MA-240, MA-240-0-1, MA-240-701, MA-240-701-1, MA-243, MA-243-0-1, MA-243-701, MAH-241-0-1, MAH-241-701, and MAH-241-701-1. The Actuators have manufacture date codes of 9348 through 9947. The Actuators were manufactured in the United States.

The MA 200 series Actuators were used in fire/smoke dampers manufactured by the following companies between December 1993 and October 1999:

Company Location
Accurate Specialty Metal
Arlan Damper Corp
ASL (Tomkins) Limited (Air Systems, Ltd.)
ASL (Tomkins) Limited (Air Systems, Ltd.)
Cesco Products
Greenheck Fan Corp.
Leader Industries
Metalpress Export Ltd.
Nailor Industries
NCA Manufacturing Limited Canada
NCA Manufacturing
Pacific Air Balance, Inc.
P.C.I. (Pottorff).
Prefco Products
Reed National Air Products Group
Ruskin Manufacturing
Brooklyn, NY
Bohemia, NY
New Westminster, BC, Canada
Brampton, ON, Canada
Minneapolis, MN
Schofield, WI
Nashville, TN
Bat Yam, Israel
Houston, TX
Missaugua, ON Canada
Garland, TX
San Fernando, CA
Montebello, CA
Buckingham, PA
Holland, OH
Grandview, MO


Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200. To be eligible for a free actuator replacement, the building owner must test the actuator per program procedures, and report the results to Invensys' Program Coordination Office on the required forms. Invensys will replace those actuators that fail to properly function during testing.

Building owners with dampers manufactured by Ruskin Manufacturing Co. may have already participated in a similar Replacement Actuator Program conducted by Ruskin. Those building owners also should review this announcement and participate in this recall, as it provides follow-up on Ruskin's program.

Different Views of Recalled Actuator
MA-200-series actuators attached on fire and smoke dampers. Note: Mounting arrangements vary.





Notice and Disclaimer: The information provided in these pages is preliminary and informational only. No liability is offered or assumed for inaccuracies in this information. Please check with the federal Consumer Product Safety Commission to confirm the completeness of all information provided.
Privacy Policy: This website does not collect any personally identifiable information about its visitors. No cookies nor downloaded files are sent to our users. If you have any questions or you wish to contact us about this site- please email us at the email address found on our sponsor's website.
Copyright © 2005-2019: by Accident Lawyer Hawaii - Construction Accident Lawyer Honolulu HI William H. Lawson



Please support our sponsors. The information on these pages is primarily brought to you by the following sponsors:
Automotive Safety Recalls - Unsafe Vehicles and Auto Parts - Hawaii Spinal Cord Injury Lawyer - SCI Attorney Honolulu - Hawaii Elevator Accident Lawyer - Escalator Accident Attorney Honolulu - Hawaii Truck Accident Attorney - Bus Accident Lawyer Honolulu - Hawaii Drowning Lawyer - Diving and Swimming Pool Accident Attorney Honolulu - Hawaii Brain Injury Lawyer - Hawaii - Brain Injury Attorney Honolulu - Hawaii Wrongful Death Lawyer - Hawaii - Wrongful Death Attorney Honolulu - Hawaii Motorcycle Accident Attorney - Motorbike Accident Lawyer Hawaii - Hawaii Drunk Driver Personal Injury Lawyer - Drugs, Texting and Drunk Driving - Hawaii Accident Investigation - Hawaii Claim Investigator