Safety Recalls, Product Recall Notices, Dangerous Products, Consumer Product Safety Recalls

from Accident Lawyer Hawaii - Defective Products Claims - Product Liability Attorney William H. Lawson


Home > Indoor Furniture & Fixtures > Dampers
FOR IMMEDIATE RELEASE
October 2, 2002
Release # 03-003
Invensys' Recall Hotline: (877) 481-2372
CPSC Consumer Hotline: (800) 638-2772
CPSC Media Contact: Ken Giles, (301) 504-7052

CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Invensys Building Systems, of Love Park, Ill., is recalling up to 560,000 Siebe actuators for testing and replacement, if necessary, which could be found in fire and smoke dampers. Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism, integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam, and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.

These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.

Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200.

To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.




Notice and Disclaimer: The information provided in these pages is preliminary and informational only. No liability is offered or assumed for inaccuracies in this information. Please check with the federal Consumer Product Safety Commission to confirm the completeness of all information provided.
Privacy Policy: This website does not collect any personally identifiable information about its visitors. No cookies nor downloaded files are sent to our users. If you have any questions or you wish to contact us about this site- please email us at the email address found on our sponsor's website.
Copyright © 2005-2019: by Accident Lawyer Hawaii - Construction Accident Lawyer Honolulu HI William H. Lawson



Please support our sponsors. The information on these pages is primarily brought to you by the following sponsors:
Automotive Safety Recalls - Unsafe Vehicles and Auto Parts - Hawaii Spinal Cord Injury Lawyer - SCI Attorney Honolulu - Hawaii Elevator Accident Lawyer - Escalator Accident Attorney Honolulu - Hawaii Truck Accident Attorney - Bus Accident Lawyer Honolulu - Hawaii Drowning Lawyer - Diving and Swimming Pool Accident Attorney Honolulu - Hawaii Brain Injury Lawyer - Hawaii - Brain Injury Attorney Honolulu - Hawaii Wrongful Death Lawyer - Hawaii - Wrongful Death Attorney Honolulu - Hawaii Motorcycle Accident Attorney - Motorbike Accident Lawyer Hawaii - Hawaii Drunk Driver Personal Injury Lawyer - Drugs, Texting and Drunk Driving - Hawaii Accident Investigation - Hawaii Claim Investigator